Medium Voltage(1/35kv) Power Cable-YJLY
Our medium voltage power cables (1/35kV aluminum core XLPE insulation PE sheath) are designed for efficient and safe power transmission. The use of high-quality aluminum core, combined with XLPE insulation and PE sheath ensures excellent performance and reliability in various environments. The cable has obtained many international certifications such as ISO, CE, Rhein Certification and is widely used in power distribution, construction engineering and renewable energy projects.
Share:
International Product Name
DIN standard: N2XS(F)2Y
IEC standard: MV Power Cable
NEC standard: Aluminum Conductor XLPE Insulated MV Cable
Experimental Requirements
DC resistance test: R≤0.08Ω/km
Insulation resistance test: Insulation resistance ≥1000MΩ, test voltage is 500V DC.
Tensile strength test: ≥15MPa.
Heat aging test: The insulation material is subjected to 720 hours at 90℃, and the insulation resistance after aging should remain ≥1000MΩ.
Heat resistance test: After 1 hour of testing at 130℃, there is no obvious deformation or cracking of the insulation material.
Fire test: According to IEC 60332-1 standard, the flame propagation length shall not exceed 1.0 meter.
Flame retardant performance test: According to IEC 60332-3-22 standard, the burning time of vertically arranged cables should be ≤20 seconds.
Advantage:
Safe and reliable: It complies with international fire protection standards, has excellent flame retardant properties, and effectively protects personal and equipment safety.
High efficiency and energy saving: The aluminum conductor has low resistivity, small transmission loss, and saves energy costs.
Durable and long-lasting: The XLPE insulation layer has excellent heat resistance and anti-aging properties, long service life, and reduces maintenance costs.
Strong adaptability: The PE sheath is corrosion-resistant and weather-resistant, and is suitable for various complex environments.
Technical Data
Medium Voltage Power Cable-YJLY(6/6kV & 6/10kV) | ||||||||
Number Of Cores | Conductor Diameter | Conductor Cross Section | Insulation Thickness | Resistance | Current | Sheath Thickness | Cable Outer Diameter | Weight |
(mm) | (mm²) | (mm) | (Ω/km) | (A) | (mm) | (mm) | (kg/km) | |
Single core | 6 | 25 | 3.4 | 1.2 | 120/130 | 1.6 | 20.1 | 491 |
7 | 35 | 3.4 | 0.868 | 145/155 | 1.6 | 21.7 | 548 | |
8.3 | 50 | 3.4 | 0.641 | 175/190 | 1.7 | 23 | 628 | |
9.8 | 70 | 3.4 | 0.443 | 215/235 | 1.7 | 24.7 | 732 | |
11.5 | 95 | 3.4 | 0.32 | 255/290 | 1.8 | 26.3 | 847 | |
12.9 | 120 | 3.4 | 0.253 | 290/335 | 1.8 | 27.7 | 957 | |
14.5 | 150 | 3.4 | 0.206 | 330/380 | 1.9 | 29.5 | 1098 | |
16 | 185 | 3.4 | 0.164 | 370/435 | 1.9 | 31.1 | 1241 | |
18.3 | 240 | 3.4 | 0.125 | 435/515 | 2 | 33.5 | 1470 | |
20.5 | 300 | 3.4 | 0.1 | 490/595 | 2.1 | 35.9 | 1715 | |
Three cores | 6 | 25 | 3.4 | 1.2 | 100/90 | 2.2 | 41.1 | 1549 |
7 | 35 | 3.4 | 0.868 | 120/110 | 2.3 | 43.3 | 1737 | |
8.3 | 50 | 3.4 | 0.641 | 140/130 | 2.4 | 46.3 | 2020 | |
9.8 | 70 | 3.4 | 0.443 | 170/165 | 2.5 | 50.4 | 2414 | |
11.5 | 95 | 3.4 | 0.32 | 210/220 | 2.7 | 54 | 2824 | |
12.9 | 120 | 3.4 | 0.253 | 235/225 | 2.8 | 57.2 | 3217 | |
14.5 | 150 | 3.4 | 0.206 | 260/255 | 2.9 | 60.9 | 3681 | |
16 | 185 | 3.4 | 0.164 | 300/295 | 3 | 66.5 | 4191 | |
18.3 | 240 | 3.4 | 0.125 | 345/345 | 3.2 | 69.7 | 4979 | |
20.5 | 300 | 3.4 | 0.1 | 390/390 | 3.3 | 74.6 | 5788 |
Medium Voltage Power Cable-YJLY(12/20kV) | ||||||||
Number of cores | Conductor Diameter | Conductor Cross Section | Insulation Thickness | Resistance | Current | Sheath Thickness | Cable Outer Diameter | Weight |
(mm) | (mm²) | (mm) | (Ω/km) | (A) | (mm) | (mm) | (kg/km) | |
Single core | 7 | 35 | 5.5 | 0.868 | 145/155 | 1.8 | 26.6 | 761 |
8.3 | 50 | 5.5 | 0.641 | 175/190 | 1.8 | 27.9 | 849 | |
9.8 | 70 | 5.5 | 0.443 | 215/235 | 1.9 | 29.8 | 979 | |
11.5 | 95 | 5.5 | 0.32 | 255/290 | 1.9 | 31.4 | 1107 | |
12.9 | 120 | 5.5 | 0.253 | 290/335 | 2 | 33 | 1241 | |
14.5 | 150 | 5.5 | 0.206 | 330/380 | 2 | 34.6 | 1382 | |
16 | 185 | 5.5 | 0.164 | 370/435 | 2.1 | 36.4 | 1553 | |
18.3 | 240 | 5.5 | 0.125 | 435/515 | 2.2 | 38.8 | 1803 | |
20.5 | 300 | 5.5 | 0.1 | 490/595 | 2.2 | 41 | 2050 | |
23.5 | 400 | 5.5 | 0.0778 | 565/695 | 2.3 | 45.4 | 2553 | |
Three cores | 7 | 35 | 5.5 | 0.868 | 120/110 | 2.7 | 54.7 | 2571 |
8.3 | 50 | 5.5 | 0.641 | 140/130 | 2.8 | 57.7 | 2899 | |
9.8 | 70 | 5.5 | 0.443 | 170/165 | 2.9 | 61.5 | 3330 | |
11.5 | 95 | 5.5 | 0.32 | 210/220 | 3 | 65.2 | 3796 | |
12.9 | 120 | 5.5 | 0.253 | 235/225 | 3.1 | 68.4 | 4237 | |
14.5 | 150 | 5.5 | 0.206 | 260/255 | 3.2 | 72 | 4753 | |
16 | 185 | 5.5 | 0.164 | 300/295 | 3.3 | 75.7 | 5319 | |
18.3 | 240 | 5.5 | 0.125 | 345/345 | 3.5 | 80.8 | 6182 | |
20.5 | 300 | 5.5 | 0.1 | 390/390 | 3.7 | 86 | 7103 | |
23.5 | 400 | 5.5 | 0.0778 | 445/450 | 3.9 | 93.2 | 8531 |
Medium Voltage Power Cable-YJLY(8.7/10kV & 8.7/15kV) | ||||||||
Number of cores | Conductor Diameter | Conductor Cross Section | Insulation Thickness | Resistance | Current | Sheath Thickness | Cable Outer Diameter | Weight |
(mm) | (mm²) | (mm) | (Ω/km) | (A) | (mm) | (mm) | (kg/km) | |
Single core | 6 | 25 | 4.5 | 1.2 | 120/130 | 1.6 | 23.1 | 585 |
7 | 35 | 4.5 | 0.868 | 145/155 | 1.6 | 24.1 | 646 | |
8.3 | 50 | 4.5 | 0.641 | 175/190 | 1.7 | 25.4 | 729 | |
9.8 | 70 | 4.5 | 0.443 | 215/235 | 1.8 | 27.1 | 840 | |
11.5 | 95 | 4.5 | 0.32 | 255/290 | 1.8 | 28.9 | 973 | |
12.9 | 120 | 4.5 | 0.253 | 290/335 | 1.9 | 30.3 | 1087 | |
14.5 | 150 | 4.5 | 0.206 | 330/380 | 1.9 | 32.1 | 1236 | |
16 | 185 | 4.5 | 0.164 | 370/435 | 2 | 33.7 | 1385 | |
18.3 | 240 | 4.5 | 0.125 | 435/515 | 2.1 | 36.1 | 1624 | |
20.5 | 300 | 4.5 | 0.1 | 490/595 | 2.2 | 38.5 | 1879 | |
Three cores | 23.5 | 400 | 4.5 | 0.0778 | 565/695 | 2.3 | 43.1 | 2377 |
6 | 25 | 4.5 | 1.2 | 100/90 | 2.4 | 46.4 | 1893 | |
7 | 35 | 4.5 | 0.868 | 120/110 | 2.5 | 48.8 | 2116 | |
8.3 | 50 | 4.5 | 0.641 | 140/130 | 2.6 | 54.8 | 2421 | |
9.8 | 70 | 4.5 | 0.443 | 170/165 | 2.7 | 55.6 | 2821 | |
11.5 | 95 | 4.5 | 0.32 | 210/220 | 2.8 | 59.3 | 3257 | |
12.9 | 120 | 4.5 | 0.253 | 235/225 | 2.9 | 62.5 | 3672 | |
14.5 | 150 | 4.5 | 0.206 | 260/255 | 3 | 66.4 | 4190 | |
16 | 185 | 4.5 | 0.164 | 300/295 | 3.2 | 70 | 4726 | |
18.3 | 240 | 4.5 | 0.125 | 345/345 | 3.3 | 75.1 | 5551 | |
20.5 | 300 | 4.5 | 0.1 | 390/390 | 3.5 | 80.1 | 6397 |
Medium Voltage Power Cable-YJLY(18/20kV & 18/30kV) | ||||||||
Number of cores | Conductor Diameter | Conductor Cross Section | Insulation Thickness | Resistance | Current | Sheath Thickness | Cable Outer Diameter | Weight |
(mm) | (mm²) | (mm) | (Ω/km) | (A) | (mm) | (mm) | (kg/km) | |
Single core | 8.3 | 50 | 0.641 | 175/190 | 2 | 35.1 | 1253 | |
9.8 | 70 | 0.443 | 215/235 | 2.1 | 37 | 1405 | ||
11.5 | 95 | 0.32 | 255/290 | 2.1 | 38.6 | 1550 | ||
12.9 | 120 | 0.253 | 290/335 | 2.2 | 40.2 | 1703 | ||
14.5 | 150 | 0.206 | 330/380 | 2.2 | 41.8 | 1863 | ||
16 | 185 | 0.164 | 370/435 | 2.3 | 43.6 | 2054 | ||
18.3 | 240 | 0.125 | 435/515 | 2.3 | 45.8 | 2312 | ||
20.5 | 300 | 0.1 | 490/595 | 2.4 | 48.2 | 2604 | ||
Three cores | 8.3 | 50 | 8 | 0.641 | 140/130 | 3.1 | 69 | 4350 |
9.8 | 70 | 8 | 0.443 | 170/165 | 3.2 | 72.5 | 4930 | |
11.5 | 95 | 8 | 0.32 | 210/220 | 3.4 | 77 | 5580 | |
12.9 | 120 | 8 | 0.253 | 235/225 | 3.5 | 80 | 6100 | |
14.5 | 150 | 8 | 0.206 | 260/255 | 3.6 | 83.5 | 6410 | |
16 | 185 | 8 | 0.164 | 300/295 | 3.7 | 87 | 7370 | |
18.3 | 240 | 8 | 0.125 | 345/345 | 3.9 | 92.2 | 8300 | |
20.5 | 300 | 8 | 0.1 | 390/390 | 4 | 97.3 | 9300 | |
23.5 | 400 | 8 | 0.0778 | 445/450 |
Medium Voltage Power Cable-YJLY(21/35kV) | ||||||||
Number of cores | Conductor Diameter | Conductor Cross Section | Insulation Thickness | Resistance | Current | Sheath Thickness | Cable Outer Diameter | Weight |
(mm) | (mm²) | (mm) | (Ω/km) | (A) | (mm) | (mm) | (kg/km) | |
Single core | 8.3 | 50 | 9.3 | 0.641 | 175/190 | 2.1 | 38.1 | 1441 |
9.8 | 70 | 9.3 | 0.443 | 215/235 | 2.1 | 40 | 1602 | |
11.5 | 95 | 9.3 | 0.32 | 255/290 | 2.2 | 41.6 | 1754 | |
12.9 | 120 | 9.3 | 0.253 | 290/335 | 2.2 | 43.2 | 1915 | |
14.5 | 150 | 9.3 | 0.206 | 330/380 | 2.3 | 44.8 | 2082 | |
16 | 185 | 9.3 | 0.164 | 370/435 | 2.3 | 46.6 | 2282 | |
18.3 | 240 | 9.3 | 0.125 | 435/515 | 2.4 | 49.2 | 2570 | |
20.5 | 300 | 9.3 | 0.1 | 490/595 | 2.5 | 51.2 | 2852 | |
Three cores | 8.3 | 50 | 9.3 | 0.641 | 140/130 | 3.3 | 75.1 | 4640 |
9.8 | 70 | 9.3 | 0.443 | 170/165 | 3.5 | 78.6 | 5160 | |
11.5 | 95 | 9.3 | 0.32 | 210/220 | 3.6 | 82.5 | 5730 | |
12.9 | 120 | 9.3 | 0.253 | 235/225 | 3.7 | 85.7 | 6262 | |
14.5 | 150 | 9.3 | 0.206 | 260/255 | 3.8 | 89.4 | 6860 | |
16 | 185 | 9.3 | 0.164 | 300/295 | 3.9 | 92.8 | 7500 | |
18.3 | 240 | 9.3 | 0.125 | 345/345 | 4.1 | 98.1 | 8520 | |
20.5 | 300 | 9.3 | 0.1 | 390/390 | 4.2 | 103.1 | 9520 |
Medium Voltage Power Cable-YJLY(26/35kV) | ||||||||
Number of cores | Conductor Diameter | Conductor Cross Section | Insulation Thickness | Resistance | Current | Sheath Thickness | Cable Outer Diameter | Weight |
(mm) | (mm²) | (mm) | (Ω/km) | (A) | (mm) | (mm) | (kg/km) | |
Single core | 8.3 | 50 | 9.3 | 0.641 | 175/190 | 2.1 | 38.1 | 1441 |
9.8 | 70 | 9.3 | 0.443 | 215/235 | 2.1 | 40 | 1602 | |
11.5 | 95 | 9.3 | 0.32 | 255/290 | 2.2 | 41.6 | 1754 | |
12.9 | 120 | 9.3 | 0.253 | 290/335 | 2.2 | 43.2 | 1915 | |
14.5 | 150 | 9.3 | 0.206 | 330/380 | 2.3 | 44.8 | 2082 | |
16 | 185 | 9.3 | 0.164 | 370/435 | 2.3 | 46.6 | 2282 | |
18.3 | 240 | 9.3 | 0.125 | 435/515 | 2.4 | 49.2 | 2570 | |
20.5 | 300 | 9.3 | 0.1 | 490/595 | 2.5 | 51.2 | 2852 | |
Three cores | 8.3 | 50 | 9.3 | 0.641 | 140/130 | 3.3 | 75.1 | 4640 |
9.8 | 70 | 9.3 | 0.443 | 170/165 | 3.5 | 78.6 | 5160 | |
11.5 | 95 | 9.3 | 0.32 | 210/220 | 3.6 | 82.5 | 5730 | |
12.9 | 120 | 9.3 | 0.253 | 235/225 | 3.7 | 85.7 | 6262 | |
14.5 | 150 | 9.3 | 0.206 | 260/255 | 3.8 | 89.4 | 6860 | |
16 | 185 | 9.3 | 0.164 | 300/295 | 3.9 | 92.8 | 7500 | |
18.3 | 240 | 9.3 | 0.125 | 345/345 | 4.1 | 98.1 | 8520 | |
20.5 | 300 | 9.3 | 0.1 | 390/390 | 4.2 | 103.1 | 9520 |
Expand all
Only some product parameters are displayed. For more product information, please contact us.
The above parameters are for reference only.
Cable Structure
1-35kv Aluminum Core XLPE Insulated PE Sheathed Power Cable
Features
Features
Widely Use:
High conductivity
The use of aluminum conductors effectively reduces energy loss and is suitable for power transmission over several kilometers.
Superior insulation
XLPE insulation can withstand operating temperatures up to 90°C and has excellent anti-aging properties, making it suitable for long-term exposure to harsh environments.
Fire and flame retardant
This cable complies with international standards (IEC 60332) to ensure that flame spread can be slowed down in the event of a fire.
Mechanical strength
The design with steel belt armor not only increases durability, but also reduces power outages and repair costs caused by external damage.
Cost-effective
Aluminum core cables have a cost advantage over copper core cables, reducing the initial investment of the overall project.
Usage Characteristics
Rated voltage Uo/U3.6/6, 6/6, 6/10, 8.7/10, 8.7/15, 12/20, 18/20, 18/30, 21/35, 26/35kV
Maximum operating temperature 90℃
Maximum conductor temperature 250℃ during short circuit (no more than 5 seconds)
Laying temperature not less than 0℃
Tensile strength ≥12.5N/mm²
Minimum bending radius:
Single core: 20D±5%
Three cores without armor: 15D±5%
Three cores with armor: 12D±5%
Production
Production Equipment
Experimental Equipment
Projects
COMMON QUESTIONS
SHENXING Cable Service FAQs
Want to learn more? Check out our electrical cable most frequently asked questions.
What is the rated voltage of this cable?
The rated voltage of this cable is 1/35kV, which is suitable for medium voltage power transmission.
What are the advantages of aluminum core cable?
Aluminum core cable is lighter, lower cost, has high conductivity, is suitable for long-distance power transmission, and is easier to install.
What are the characteristics of XLPE insulation material?
XLPE insulation has excellent heat resistance, aging resistance and electrical insulation performance, and can work safely in the temperature range of -40°C to 90°C.
Is this cable fireproof and flame retardant?
Yes, this cable meets the relevant fireproof and flame retardant standards and can slow down the spread of flames under fire conditions.
In what environments is this cable suitable for use?
This cable is suitable for a variety of environments, including indoors, underground and outdoors, and can resist water, ultraviolet rays and chemical corrosion.
What are the installation requirements of the cable?
During installation, national and regional electrical safety standards must be followed to ensure protection of the connection and avoid physical damage.
What is the service life of this cable?
Under normal use and maintenance, the expected service life of this cable can reach 30 years and above.
Is it possible to provide customized services?
Yes, we can customize the length, cross-section and other parameters of the cable according to the specific needs of customers.
What are the precautions for transportation and storage?